You heat the house much less, and the required heating equipment can often be specified several times smaller than in a conventional envelope.
Two zid logics
Kako zid keeps summer toplina izvan
Outdoor toplina reaches izolacija i je reflected back outward. indoor side stays cool, s calm blue zrak pomicanje i ne aktivni hlađenje redoslijed.
Thermoblock winter toplina put
betonska jezgra je separated od room prema unutarnji izolacija, zato ono cannot rad like warm-side accumulator u Passive House Block.
Inertial house explained.
When heating turns off, a warm-side concrete core can keep working as a slow thermal accumulator. Exterior insulation keeps that core inside the protected envelope; inner insulation breaks the direct exchange between the room and the structural mass.
Same core, different behavior
The same concrete core behaves differently when insulation is outside it versus split around it.
Mass inside the envelope
With exterior insulation, the load-bearing core belongs to the indoor thermal zone. With split inner/outer insulation, the room is insulated from the concrete, so the core is less available for comfort, heat storage and moisture-safe temperature control.
Choose your wall strategy.
Odaberite klimu, performanse cilj i projektiranje priority u vidjeti koji Passive House Block zidni sustav je best starting point.
NZEB Wall System - 200 mm
Best default balance for many low-energy European projects.
Indicative insulation-layer U-value: 0.160 W/m²KIndikativan smjernice samo. Konačni performanse zida mora biti provjereno za cjeloviti sklop zida, uključujući betonsku jezgru, završne obrade, geometriju, spojeve, toplinski mostovi, zrakonepropusnost i lokalni izračun method.
Four insulation levels, one envelope logic.
Odaberite debljina izolacije prema klimu, ciljanu U-vrijednost i strategiju zida. Indikativan layer-only vrijednosti use graphite EPS / Neopor, λ = 0.032 W/m·K.
150 mm insulation option
RSI / metric R: 4.69 m²K/W
US R-value: R-26.6
Indicative U-value: 0.213 W/m²KBest for: warm climates, compact walls, above-code projects.Watch out: not intended as the strongest passive-house-oriented option for colder climates.
200 mm insulation option
RSI / metric R: 6.25 m²K/W
US R-value: R-35.5
Indicative U-value: 0.160 W/m²KBest for: balanced low-energy European housing.Watch out: final performance still depends on windows, roof, slab, airtightness and thermal bridges.
250 mm insulation option
RSI / metric R: 7.81 m²K/W
US R-value: R-44.4
Indicative U-value: 0.128 W/m²KBest for: lower heat loss, cooler climates and stronger envelope targets.Watch out: wall thickness and detailing should be coordinated early with openings and foundations.
300 mm insulation option
RSI / metric R: 9.38 m²K/W
US R-value: R-53.2
Indicative U-value: 0.107 W/m²KBest for: maximum envelope performance and passive-house-oriented wall assemblies.Watch out: layer-only values are not a full building certification.
No certification claim: RSI, R-value and U-value figures are indicative and calculated for the insulation layer only. Final wall performance must be calculated for the complete wall build-up according to EN ISO / HRN EN ISO 6946, including concrete core, finishes, geometry, junctions and thermal bridges.
U-value benchmarks, side by side.
Niži U-vrijednost znači manji toplinski gubitak. comparison ispod je referentna vrijednost guide, ne certifikacija statement.
| Benchmark reference | Target | Energy+0.213 | NZEB0.160 | NZEB+0.128 | PHB0.107 |
|---|---|---|---|---|---|
| UK Part L — limiting wall value, new dwellings | U ≤ 0.26 W/m²K | Pass | Pass | Pass | Pass |
| UK Part L — extensions / new fabric elements in existing dwellings | U ≤ 0.18 W/m²K | No | Pass | Pass | Pass |
| Germany GEG — reference residential external wall | U = 0.28 W/m²K | Pass | Pass | Pass | Pass |
| Germany GEG — external wall renovation / component benchmark | U ≤ 0.24 W/m²K | Pass | Pass | Pass | Pass |
| Ireland TGD L — new dwelling wall average | U ≤ 0.18 W/m²K | No | Pass | Pass | Pass |
| Croatia — strict end of new-building wall range | U ≤ 0.30 W/m²K | Pass | Pass | Pass | Pass |
| Italy — strict end of new-building wall range | U ≤ 0.24 W/m²K | Pass | Pass | Pass | Pass |
| Netherlands — new-building wall benchmark | U ≤ 0.22 W/m²K | Pass | Pass | Pass | Pass |
| Sweden — new-building wall benchmark | U ≤ 0.18 W/m²K | No | Pass | Pass | Pass |
| Finland — stricter end of new-building wall range | U ≤ 0.17 W/m²K | No | Pass | Pass | Pass |
| Luxembourg — high-performance wall benchmark | U ≤ 0.13 W/m²K | No | No | Pass | Pass |
| PHI warm-temperate component benchmark | U ≤ 0.25 W/m²K | Pass | Pass | Pass | Pass |
| PHI cool-temperate Passive House benchmark | U ≤ 0.15 W/m²K | No | Close | Pass | Pass |
| PHI cold-climate component benchmark | U ≤ 0.12 W/m²K | No | No | Close | Pass |
| PHI arctic component benchmark | U ≤ 0.09 W/m²K | No | No | No | No |
Benchmark guide, not certification.
The comparison shows indicative insulation-layer U-values only. Passing a benchmark row does not mean product certification, project certification or full building compliance.
Warm walls are not only for cold countries.
Less heat loss, warmer internal surfaces and lower heating demand.
Slower heat gain, lower air-conditioning demand and more stable indoor temperature.
Lower condensation risk, calmer internal surfaces and reduced mould risk.
Lower demand before technology has to work.
Toplina pumps, zrak handlers, photovoltaics i smart controls može biti excellent choices, ali oni i dalje have service lives, maintenance treba, uporabni limits i replacement cycles.
Ako ovojnica je slab, oprema mora constantly compensate za toplina gubitak, overheating, drafts i toplinski mostovi.
jak zid ovojnica quietly lowers toplina gubitak every hour od building's life. Ono has ne compressor, ne software, ne filter, ne moving parts i ne service interval.
Better izolacija makes every later sustav smaller, calmer i less critical.
Practical sequence: reduce losses first, then size systems. The more the building does passively, the less mechanical equipment has to correct actively.
Same R-value, different thickness.
Različit izolacija i masonry materijali može reach isti R-vrijednost s različit debljine. Ovo comparison je fizika referenca, ne puni zidni sklop specifikacija.
Formula cardRSI = layer thickness / λ. U-value = 1 / RSI.Graphite EPS / Neopor remains the reference material. The table below compares layer-only thicknesses needed to reach the same target RSI.
| Material / wall type | Typical lambda | Notes |
|---|---|---|
| Graphite EPS / Neopor | 0.032 W/m·K | Reference value used for the Passive House Block wall-system options above. |
| White EPS | 0.039 W/m·K | Requires more thickness to reach the same insulation resistance. |
| Mineral wool (ideal dry) | 0.040 W/m·K | Ideal dry-condition calculation for facade basalt/mineral wool. |
| Mineral wool (wet / dew point) | 0.060 W/m·K | Installation error or dew point inside the insulation layer: moisture raises lambda and the same R-value needs more thickness. |
| PIR / PUR board | 0.022 W/m·K | Higher thermal resistance per millimetre; assembly, cost and fire detailing must be considered. |
| Wood fibre insulation | 0.040 W/m·K | Can support bio-based wall strategies, but needs careful moisture and assembly design. |
| Autoclaved aerated concrete (gas block) | 0.150 W/m·K | Lightweight masonry with better insulation than dense masonry, but a very thick wall is needed to match RSI 6.25 without added insulation. |
| Clay brick masonry | 0.650 W/m·K | Brick is useful for structure, durability and thermal mass; by itself it is not an efficient insulation layer. |
| Hollow ceramic brick | 0.240 W/m·K | Voids improve thermal resistance compared with dense brick, but the wall still needs substantial thickness or added insulation. |
| Ytong AAC block | 0.090 W/m·K | High-insulation AAC product class; exact lambda depends on density and the selected Ytong block. |
Formula: RSI = layer thickness / λ. U-value = 1 / RSI. Fixed target: 200 mm NZEB reference, RSI 6.25 (U-value 0.160 W/m²K). Each material gets a fixed 0-6 m drawing scale; thickness values are layer-only equivalents using RSI = thickness / λ. In a real wall, the final result must include all layers and thermal bridges.
How much wall is needed to match
300 mm Passive House Block insulation?

Mineral wool, gas blok / AAC i Ytong rely na air-filled fibres ili pores. Ako točka rosišta sits unutar to sloj i kondenzacija wets ono, voda replaces zrak, effective λ rises i materijal može lose much od njegov izolacija vrijednost until ono dries.
Weak Points Lab
Frames should connect to the insulation line, not sit as a cold bridge at the structural edge.
The bottom connection is often where insulation, airtightness and water protection fail.
Foundation and wall insulation must connect continuously.
The thermal envelope must remain continuous at the top of the wall.
Structural penetrations can create major thermal bridges if not detailed.
Pipes, cables and ducts need airtight and insulated detailing.
Good insulation cannot compensate for uncontrolled air leakage.
The assembly must be checked so moisture does not reduce insulation performance.
Efficiency that remains when systems are off.
Kada zid loses less toplina, every tehnički sustav becomes lakše u size, operate i maintain. Efficiency počinje s fizika, ne oprema.
Better izolacija keeps internal surfaces toplije u winter i calmer u summer, improving udobnost prije aktivni conditioning je considered.
robust ovojnica i dalje performs during maintenance, grid stress, commissioning issues ili budući oprema changes.
From wall U-value to real building performance.
nizak zid U-vrijednost nije puni zgrada certificate. Konačni performanse ovisi na cjeloviti sklop zida, prozori, roof, temelj, zrakonepropusnost, toplinski mostovi, ventilacija strategija i lokalni izračun method.
All layers, not only insulation.
Openings must meet the insulation line.
The top envelope must continue the wall logic.
The base connection must avoid bypasses.
Air leakage can defeat good U-values.
Junctions and brackets need calculation.
Comfort and moisture depend on air management.
Compliance depends on the local method.
Reference standards, not marketing claims.
Toplinski resistance i toplinski transmittance izračun method za zgrada components.
Opaque gradnja sustav kriteriji i klimu-dependent U-vrijednost referentne vrijednosti.
Wall U-value reference points for new dwellings and notional dwelling comparison.
External wall component U-value benchmark for renovation / first installation cases.
Project notes and deeper technical pages.
Breathing Zidovi i VentilacijaWhy walls should be vapour-safe but not air-leaky, and why fresh air belongs in controlled ventilation.Read page
Objašnjenje točke rosištaCondensation risk, wet insulation behaviour and why internal wall insulation needs special care.Read page
Zidovi Passive House BlockExterior insulation, reinforced concrete core and the build logic behind the main wall system.Read page
Kontinuirana toplinska ovojnicaHow insulation, airtightness and thermal-bridge control stay continuous around the building.Read page
Topla ugradnja prozora i vrataInstallation detail for frames, insulation-line connection and airtight-layer sealing.Read page
Izolirani temeljGround heat-loss control and continuity between the foundation and wall envelope.Read page
Insulated Swedish Slab FoundationUShP as a warm base with continuous insulation, services and warm-floor heating.Read page
Warm Window InstallationWhy the frame belongs in the insulation plane instead of the structural wall edge.Read page





















