You heat the house much less, and the required heating equipment can often be specified several times smaller than in a conventional envelope.
Two wall logics
How the wall keeps summer heat outside
Outdoor heat reaches the insulation and is reflected back outward. The indoor side stays cool, with calm blue air movement and no active cooling sequence.
Thermoblock winter heat path
The concrete core is separated from the room by inner insulation, so it cannot work like the warm-side accumulator in Passive House Block.
Inertial house explained.
When heating turns off, a warm-side concrete core can keep working as a slow thermal accumulator. Exterior insulation keeps that core inside the protected envelope; inner insulation breaks the direct exchange between the room and the structural mass.
Same core, different behavior
The same concrete core behaves differently when insulation is outside it versus split around it.
Mass inside the envelope
With exterior insulation, the load-bearing core belongs to the indoor thermal zone. With split inner/outer insulation, the room is insulated from the concrete, so the core is less available for comfort, heat storage and moisture-safe temperature control.
Choose your wall strategy.
Select the climate, performance target and design priority to see which Passive House Block wall system is the best starting point.
NZEB Wall System - 200 mm
Best default balance for many low-energy European projects.
Indicative insulation-layer U-value: 0.160 W/m²KIndicative guidance only. Final wall performance must be verified for the complete wall build-up, including concrete core, finishes, geometry, junctions, thermal bridges, airtightness and local calculation method.
Four insulation levels, one envelope logic.
Choose the insulation thickness by climate, target U-value and wall strategy. Indicative layer-only values use graphite EPS / Neopor, λ = 0.032 W/m·K.
150 mm insulation option
RSI / metric R: 4.69 m²K/W
US R-value: R-26.6
Indicative U-value: 0.213 W/m²KBest for: warm climates, compact walls, above-code projects.Watch out: not intended as the strongest passive-house-oriented option for colder climates.
200 mm insulation option
RSI / metric R: 6.25 m²K/W
US R-value: R-35.5
Indicative U-value: 0.160 W/m²KBest for: balanced low-energy European housing.Watch out: final performance still depends on windows, roof, slab, airtightness and thermal bridges.
250 mm insulation option
RSI / metric R: 7.81 m²K/W
US R-value: R-44.4
Indicative U-value: 0.128 W/m²KBest for: lower heat loss, cooler climates and stronger envelope targets.Watch out: wall thickness and detailing should be coordinated early with openings and foundations.
300 mm insulation option
RSI / metric R: 9.38 m²K/W
US R-value: R-53.2
Indicative U-value: 0.107 W/m²KBest for: maximum envelope performance and passive-house-oriented wall assemblies.Watch out: layer-only values are not a full building certification.
No certification claim: RSI, R-value and U-value figures are indicative and calculated for the insulation layer only. Final wall performance must be calculated for the complete wall build-up according to EN ISO / HRN EN ISO 6946, including concrete core, finishes, geometry, junctions and thermal bridges.
U-value benchmarks, side by side.
Lower U-value means lower heat loss. The comparison below is a benchmark guide, not a certification statement.
| Benchmark reference | Target | Energy+0.213 | NZEB0.160 | NZEB+0.128 | PHB0.107 |
|---|---|---|---|---|---|
| UK Part L — limiting wall value, new dwellings | U ≤ 0.26 W/m²K | Pass | Pass | Pass | Pass |
| UK Part L — extensions / new fabric elements in existing dwellings | U ≤ 0.18 W/m²K | No | Pass | Pass | Pass |
| Germany GEG — reference residential external wall | U = 0.28 W/m²K | Pass | Pass | Pass | Pass |
| Germany GEG — external wall renovation / component benchmark | U ≤ 0.24 W/m²K | Pass | Pass | Pass | Pass |
| Ireland TGD L — new dwelling wall average | U ≤ 0.18 W/m²K | No | Pass | Pass | Pass |
| Croatia — strict end of new-building wall range | U ≤ 0.30 W/m²K | Pass | Pass | Pass | Pass |
| Italy — strict end of new-building wall range | U ≤ 0.24 W/m²K | Pass | Pass | Pass | Pass |
| Netherlands — new-building wall benchmark | U ≤ 0.22 W/m²K | Pass | Pass | Pass | Pass |
| Sweden — new-building wall benchmark | U ≤ 0.18 W/m²K | No | Pass | Pass | Pass |
| Finland — stricter end of new-building wall range | U ≤ 0.17 W/m²K | No | Pass | Pass | Pass |
| Luxembourg — high-performance wall benchmark | U ≤ 0.13 W/m²K | No | No | Pass | Pass |
| PHI warm-temperate component benchmark | U ≤ 0.25 W/m²K | Pass | Pass | Pass | Pass |
| PHI cool-temperate Passive House benchmark | U ≤ 0.15 W/m²K | No | Close | Pass | Pass |
| PHI cold-climate component benchmark | U ≤ 0.12 W/m²K | No | No | Close | Pass |
| PHI arctic component benchmark | U ≤ 0.09 W/m²K | No | No | No | No |
Benchmark guide, not certification.
The comparison shows indicative insulation-layer U-values only. Passing a benchmark row does not mean product certification, project certification or full building compliance.
Warm walls are not only for cold countries.
Less heat loss, warmer internal surfaces and lower heating demand.
Slower heat gain, lower air-conditioning demand and more stable indoor temperature.
Lower condensation risk, calmer internal surfaces and reduced mould risk.
Lower demand before technology has to work.
Heat pumps, air handlers, photovoltaics and smart controls can be excellent choices, but they still have service lives, maintenance needs, operating limits and replacement cycles.
If the envelope is weak, equipment must constantly compensate for heat loss, overheating, drafts and thermal bridges.
A strong wall envelope quietly lowers heat loss every hour of the building's life. It has no compressor, no software, no filter, no moving parts and no service interval.
Better insulation makes every later system smaller, calmer and less critical.
Practical sequence: reduce losses first, then size systems. The more the building does passively, the less mechanical equipment has to correct actively.
Same R-value, different thickness.
Different insulation and masonry materials can reach the same R-value with different thicknesses. This comparison is a physics reference, not a full wall assembly specification.
Formula cardRSI = layer thickness / λ. U-value = 1 / RSI.Graphite EPS / Neopor remains the reference material. The table below compares layer-only thicknesses needed to reach the same target RSI.
| Material / wall type | Typical lambda | Notes |
|---|---|---|
| Graphite EPS / Neopor | 0.032 W/m·K | Reference value used for the Passive House Block wall-system options above. |
| White EPS | 0.039 W/m·K | Requires more thickness to reach the same insulation resistance. |
| Mineral wool (ideal dry) | 0.040 W/m·K | Ideal dry-condition calculation for facade basalt/mineral wool. |
| Mineral wool (wet / dew point) | 0.060 W/m·K | Installation error or dew point inside the insulation layer: moisture raises lambda and the same R-value needs more thickness. |
| PIR / PUR board | 0.022 W/m·K | Higher thermal resistance per millimetre; assembly, cost and fire detailing must be considered. |
| Wood fibre insulation | 0.040 W/m·K | Can support bio-based wall strategies, but needs careful moisture and assembly design. |
| Autoclaved aerated concrete (gas block) | 0.150 W/m·K | Lightweight masonry with better insulation than dense masonry, but a very thick wall is needed to match RSI 6.25 without added insulation. |
| Clay brick masonry | 0.650 W/m·K | Brick is useful for structure, durability and thermal mass; by itself it is not an efficient insulation layer. |
| Hollow ceramic brick | 0.240 W/m·K | Voids improve thermal resistance compared with dense brick, but the wall still needs substantial thickness or added insulation. |
| Ytong AAC block | 0.090 W/m·K | High-insulation AAC product class; exact lambda depends on density and the selected Ytong block. |
Formula: RSI = layer thickness / λ. U-value = 1 / RSI. Fixed target: 200 mm NZEB reference, RSI 6.25 (U-value 0.160 W/m²K). Each material gets a fixed 0-6 m drawing scale; thickness values are layer-only equivalents using RSI = thickness / λ. In a real wall, the final result must include all layers and thermal bridges.
How much wall is needed to match
300 mm Passive House Block insulation?

Mineral wool, gas block / AAC and Ytong rely on air-filled fibres or pores. If the dew point sits inside that layer and condensation wets it, water replaces air, effective λ rises and the material can lose much of its insulation value until it dries.
Weak Points Lab
Frames should connect to the insulation line, not sit as a cold bridge at the structural edge.
The bottom connection is often where insulation, airtightness and water protection fail.
Foundation and wall insulation must connect continuously.
The thermal envelope must remain continuous at the top of the wall.
Structural penetrations can create major thermal bridges if not detailed.
Pipes, cables and ducts need airtight and insulated detailing.
Good insulation cannot compensate for uncontrolled air leakage.
The assembly must be checked so moisture does not reduce insulation performance.
Efficiency that remains when systems are off.
When the wall loses less heat, every technical system becomes easier to size, operate and maintain. Efficiency starts with physics, not equipment.
Better insulation keeps internal surfaces warmer in winter and calmer in summer, improving comfort before active conditioning is considered.
A robust envelope still performs during maintenance, grid stress, commissioning issues or future equipment changes.
From wall U-value to real building performance.
A low wall U-value is not a full building certificate. Final performance depends on the complete wall build-up, windows, roof, foundation, airtightness, thermal bridges, ventilation strategy and the local calculation method.
All layers, not only insulation.
Openings must meet the insulation line.
The top envelope must continue the wall logic.
The base connection must avoid bypasses.
Air leakage can defeat good U-values.
Junctions and brackets need calculation.
Comfort and moisture depend on air management.
Compliance depends on the local method.
Reference standards, not marketing claims.
Thermal resistance and thermal transmittance calculation method for building components.
Opaque construction system criteria and climate-dependent U-value benchmarks.
Wall U-value reference points for new dwellings and notional dwelling comparison.
External wall component U-value benchmark for renovation / first installation cases.
Project notes and deeper technical pages.
Breathing Walls and VentilationWhy walls should be vapour-safe but not air-leaky, and why fresh air belongs in controlled ventilation.Read page
Dew Point ExplainedCondensation risk, wet insulation behaviour and why internal wall insulation needs special care.Read page
Passive House Block WallsExterior insulation, reinforced concrete core and the build logic behind the main wall system.Read page
Continuous Thermal EnvelopeHow insulation, airtightness and thermal-bridge control stay continuous around the building.Read page
Warm Window & Door InstallationInstallation detail for frames, insulation-line connection and airtight-layer sealing.Read page
Insulated FoundationGround heat-loss control and continuity between the foundation and wall envelope.Read page
Insulated Swedish Slab FoundationUShP as a warm base with continuous insulation, services and warm-floor heating.Read page
Warm Window InstallationWhy the frame belongs in the insulation plane instead of the structural wall edge.Read page





















